Kinco PLC -DC24V (14*DI 10*Do) + (4*AI 2*AO) +2pulse High Speed Output/Input Programmable Logic Controller PLC
This product is no longer promoted on Made-in-China.com. If you find any infringement or
sensitive information of it, please contact us
for
handling. Thank you.
Kinco Electric (Shenzhen) Ltd.
Guangdong, China
Last Login Date:
Jul 07, 2025
Main Products:
HMI, Motion Control, PLC, AC&DC Servo System, AC Drive, Machine Automation Solution, Frameless Motor, Kinco, VFD, Stepper System
Find Similar Products
Product Description
Company Info
Basic Info.
Model NO.
K506EA-30DT
Task
Structure
Mathematical Model
Linear
Signal
Function
Automatic Control, Protection, Monitoring, Measurement
Certification
ISO: 9001, CE
Condition
Customized
Material
Plastics
Model
Kinco PLC
Brand Name
Kinco
CPU
CPU506
Trademark
Kinco
Origin
China
Product Description
Various module types
Kinco-K5 series PLCs comprise of CPU modules and expansion modules. Kinco-K5 provides about 20 kinds of models to meet various applications. CPU modules integrate with a certain number of I/O points on body. If I/O points are not enough for application, user could connect up to 10 expansion modules with up to 200 points to meet most automation applications.
Kinco-K5 series PLCs comprise of CPU modules and expansion modules. Kinco-K5 provides about 20 kinds of models to meet various applications. CPU modules integrate with a certain number of I/O points on body. If I/O points are not enough for application, user could connect up to 10 expansion modules with up to 200 points to meet most automation applications.
Integrated DC24V Sensor Supply
CPU modules provides DC24V power supply (Terminal
name: VO+, VO-), with maximum current 300mA or
500mA. It can supply DC24V for the connected text
dispaly panel, HMI, as well as DI points.
CPU modules provides DC24V power supply (Terminal
name: VO+, VO-), with maximum current 300mA or
500mA. It can supply DC24V for the connected text
dispaly panel, HMI, as well as DI points.
Requirement on Application Environment
Climatic conditions, electrical service conditions, mechanical service conditions and so on comply with IEC61131-2 standard
Transport and storage | ||
Climatic conditions | Temperature | Temperature -40ºC~+70ºC |
Relative humidity | 10%~95%, non-condesing | |
Atmospheric Pressure | Correspond to altitude 0~3000m | |
Mechanical conditions | Free drop | Away from 1m height drop to cement floor for 5 times with transportation package |
Operation | ||
Climatic conditions | Temperature | Opening device with natural ventilation, ambient temperature: -10~55ºC |
Relative humidity | 10%~95%, non-condensing | |
Atmospheric pressure | Altitude below 2000m | |
Pollution degree | Applicable to pollution degree 2 | |
Mechanical service conditions | Vibrations | 5 < f < 8.4Hz, random amplitude: 3.5mm displacement, constant amplitude: 1.75mm displacement 8.4 < f < 150, random amplitude: 1.0g acceleration, constant amplitude: 0.5g acceleration |
Shock | Half-sine, 15g peak, 11ms duration, six shocks in each direction per axis. | |
Electromagnetic compatibility (EMC) | Electrostatic discharge | Air: 8kV, Contact: 4kV, Performance criteria B |
Surge | AC supply: 2KV CM, 1KV DM DC supply: 0.5KV CM, 0.5KV DM I/O and communication port: 1KV CM Performance criteria B | |
Fast transient bursts | Power coupling: 2KV, 5KHz I/O and communication port: 1KV, 5KHz Performance criteria B | |
Voltage Dips and interruptions | AC supply, At 50Hz,0%voltage for 1 period, 40%voltage for 10 periods, 70%voltage for 20 periods. Performance criteria A | |
Radiofrequency electromagnetic field | 80~1000 MHz,l0V/m, modulate by 1KHz sine wave. Performance criteria A | |
Protection class | Dust and water proof | IP20 |
CE Certification | ||
LVD | Test Standard: Safety requirements of EN 61131-2:2007 | |
EMC | Test Standard: Clause 8,9 &10 of EN61131-2:2007 |
Kinco-K5 series PLCs are upgraded products of K3 series.
Specially, K506EA-30AT CPU module, integrated with
analog I/O on body, pulse output, high-speed counter, is a kind of versatile micro integrated PLC (Programmable Logic Controller), and can fully meet requirements of small devices and process control.
Kinco-K5 combines with MT4000 HMI, CD/FD/JD servo driver and inverter to provider users with easy automation solutions.
Name Order no. Description | ||
CPU module | ||
CPU504EX | K504EX-14AT | AC85-265V power supply, DI 8*DC24V, DO 6*DC24V. 2 serial communication ports (1*RS232, 1*RS485), up to 4 expansion modules connectable. |
K504EX-14AR | AC85-265V power supply, DI 8*DC24V, DO 6*Relay. 2 serial communication ports (1*RS232, 1*RS485), up to 4 expansion modules connectable. | |
K504EX-14DT | DC20.4-28.8V power supply, DI8*DC24V, DO6*DC24V, 2 serial communication ports (1*RS232, 1*RS485), up to 4 expansion modules connectable. | |
K504EX-14DR | DC20.4-28.8V power supply, DI8*DC24V, DO6*Relay. 2 serial communication ports (1*RS232, 1*RS485), up to 4 expansion modules connectable. | |
CPU506 | K506-24AT | AC85-265V power supply, DI 14*DC24V, DO 10*DC24V. 3 serial communication ports (1*RS232, 2*RS485), up to 12 expansion modules connectable. |
K506-24AR | AC85-265V power supply, DI 14*DC24V, DO 10* Relay. 3 serial communication ports(1*RS232, 2*RS485), up to 10 expansion modules connectable. | |
K506-24DT | DC20.4-28.8V power supply, DI 14*DC24V, DO 10*DC24V. 3 serial communication ports(1*RS232, 2*RS485). , up to 12 expansion modules connectable. | |
K506-24DR | DC20.4-28.8V power supply, DI 14*DC24V, DO 10*Relay. 3 serial communication ports(1*RS232, 2*RS485), up to 10 expansion modules connectable. | |
CPU506EA | K506EA-30AT | AC85-265V power supply, DI 14*DC24V, DO 10*DC24V, AI 4*IV, AO 2*IV. 3 serial communication ports(1*RS232, 2*RS485), up to 12 expansion modules connectable. |
K506EA-30DT | DC20.4-28.8V power supply, DI 14*DC24V, DO 10*DC24V, AI 4*IV, AO 2*IV. 3 serial communication ports(1*RS232, 2*RS485), up to 10 expansion modules connectable. | |
CPU508 | K508-40AT | AC85-265V power supply, DI 24*DC24V, DO 16*DC24V. 3 serial communication ports(1*RS232, 2*RS485), up to 12 expansion modules connectable. |
K508-40AX | AC85-265V power supply, DI 24*DC24V, DO 4*DC24V+12*Relay. 3 serial communication ports(1*RS232, 2*RS485), up to 10 expansion modules connectable. | |
K508-40AR | AC85-265V power supply, DI 24*DC24V, DO 16*Relay. 3 serial communication ports(1*RS232, 2*RS485), up to 12 expansion modules connectable. | |
K508-40DT | DC20.4-28.8V power supply, DI 24*DC24V, DO 16*DC24V. 3 serial communication ports(1*RS232, 2*RS485), up to 10 expansion modules connectable. | |
K508-40DR | DC20.4-28.8V power supply, DI 24*DC24V, DO 16*Relay. 3 serial communication ports(1*RS232, 2*RS485), up to 12 expansion modules connectable. |
Name Order no. Description | ||
Expansion I/O module | ||
PM521 | K521-08DX | DI 8*DC24V |
K521-16DX | DI 16*DC24V | |
PM522 | K522-08XR | DO 8*relay |
K522-16XR | DO 16*relay | |
K522-08DT | DO 8*DC24V | |
K522-16DT | DO 16*DC24V | |
PM523 | K523-16DR | DI 8*DC24V,DO 8*relay |
K523-08DR | DI 4*DC24V,DO 4*relay | |
K523-16DT | DI 8*DC24V,DO 8*DC24V | |
K523-08DT | DI 4*DC24V,DO 4*DC24V | |
PM531 | K531-04IV | 4 analog input channels,4-20mA/1-5V/0-20mA/0-10V |
K531-04RD | PT100, PT1000, Cu50, Resistor | |
K531-04TC | 4 thermocouple input channels, internal/external compensation selectable, J type, K type, E type, S type | |
PM532 | K532-02IV | 2 analog output channels,4-20mA/1-5V/0-20mA/0-10V |
PM533 | K533-04IV | 2 analog input channels,4-20mA/1-5V/0-20mA/0-10V 2 analog output channels,4-20mA/1-5V/0-20mA/0-10V |
Expansion function module | ||
SM541 | K541 | CAN communication expansion module, supports CANopen master and CAN free protocol. |
Power supplier module | ||
PS580 | K580 | Input voltage:AC85~265V;output rated current:5V 1A/24V 250mA |
Front view
The following diagram is the front view of a CPU.
The following table describes main technical data of CPU model.
CPU506 | |||||
Built-in I/O and Communication | |||||
Digital channel | 14*DI/10*DO | ||||
Max. expansion modules | 10 | ||||
Communication Port | 3(PORT0, PORT1, PORT2) | ||||
PORT0 is RS232,PORT1 andPORT2 are RS485. PORT0 support the special programming protocol, Modbus RTU protocol (as a slave) and free-protocol communication mode. PORT1 andPORT2 support the special programming protocol, Modbus RTU protocol (as a slave or master) and free-protocol communication mode. | |||||
High-speed counters Single phase Two phase | 2 2, max.60KHz 2, max.20KHz | ||||
High-speed pulse output | 2,max. 200KHz.(For 200KHz, load resistance must be less than 1.5 KΩ). | ||||
I/O Interrupts | 4 channel , can be set as rising or falling edge interrupts | ||||
memory area | |||||
Max. User program | 4K instructions | ||||
User Data | M area: 1K bytes; V area: 4K bytes | ||||
DI mapping area | 32 bytes | ||||
DO mapping area | 32 bytes | ||||
AI mapping area | 64 bytes | ||||
AO mapping area | 64 bytes | ||||
Data Backup | FRAM, 448 bytes | ||||
Retentive Ranges | 4K bytes, lithium cell as backup power, 3 years at normal temperature. | ||||
Others | |||||
Timers | 256 totally: 1ms time-base: 4 ; 10ms time-base: 16; 100ms time-base: 236 | ||||
Timed interrupts | 2 with 0.1 ms resolution. | ||||
Counters | 256, (retained by lithium cell) | ||||
Real-time clock | Yes, deviation less than 2 min/month at 25°C | ||||
DC24V Sensor Supply | 300mA |
Environmental Condition
Transport and storage | ||
Ambient conditions | temperature | -40 --- +70 °C |
relative humidity | 10%~95%, no condensation | |
Altitude | Up to 3000 m | |
Mechanical conditions | Free falls | With manufacturer's original package, 5 times falling from 1m height to concrete ground. |
Normal Operation | ||
Ambient conditions | air temperature | Open equipment : -10 --- +55°C; Enclosed equipment: -10 --- +40°C |
relative humidity | 10%~95%, no condensation | |
Altitude | Up to 2000 m | |
Pollution degree | Suitable pollution degree 2. | |
Mechanical conditions | Sinusoidal vibrations | 5<f<8.4Hz, Occasional: 3.5mmamplitude; Continuous: 1.75mmmplitude. 8.4<f<150, Occasional: 1.0gacceleration; Continuous: 0.5gacceleration. |
Shock | half-sine , 15g, 11 ms, half-sine, ach axes 6 times | |
Electromagnetic compatibility (EMC) | Electrostatic discharge | ±4kV Contact, ±8kV Air. Performance Level: B |
High energy surge | a.c. main power:2KV CM, 1KV DM; d.c. main power:0.5KV CM, 0.5KV DM; I/Os and Communication port:1KVCM. Performance Level: B | |
Fast transient bursts | main power: 2KV, 5KHz. I/Os and Communication port: 1KV, 5KHz. Performance Level: B | |
Voltage drops and interruptions | a.c. power supply: at 50Hz, 0% voltage for 1 period; 40% voltage for 10 periods; 75% voltage for 20 periods. Performance criteria A. | |
ProtectionLevel | IP20 |
K506-24AR wiring diagram